You have reached the quote request page for part number CM-21A of Aerion Technologies Inc, we have in stock that is listed alongside the description Alarm Gas Automatic. If you would like to learn more about this NSN part and your purchasing options, please fill out and submit the Request the Quote (RFQ) page presented on this page. By offering us important details like your target price and expected fulfillment time frame, our team can best offer you a tailored solution for your consideration. As we have staff available at all times, responses to any submission will be offered within 15 minutes of our review.
Note : We Will Not Share Your Information With Any Third Parties.
To make exploring our expansive inventory simple, we have chosen to list all offerings alongside as much information as we can for an ease of identification. For example, part number CM-21A is specifically produced under CAGE Code 2Y359, denoting the specific Aerion Technologies Inc facility it traces back to. Furthermore, with the NSN 6665-01-530-2725, this item also belongs to FSC 6665 Hazard Detecting Instruments And Apparatus, further ensuring that you only purchase your exact needs. If you have any questions or concerns regarding our offerings or service, be sure to call or email us at your convenience. Otherwise, we look forward to serving you as your strategic sourcing partner for part number CM-21A and more.
MRC | Criteria | Characteristic |
---|---|---|
APGF | DESIGN TYPE | NONTRIPOD MOUNTING |
AFJK | III CUBIC MEASURE | 38.250 CUBIC INCHES |
SUPP | III SUPPLEMENTARY FEATURES | DIMENTIONS ARE 4.5 X 4 X 2.125 INCHES. ITEM SHOULD BE MOUNTED 4 TO 5 FEET ABOVE FLOOR LEVEL. |
FEAT | SPECIAL FEATURES | CM-21A ACTIVATES FAN RELAY AT 35 PPM OF CO AVERAGED OVER 5 MINUTES. (25 PPM IS SELECTABLE) ALARM RELAY WILL BE ACTIVATED AT 100 PPM OF CO AFTER 30 MINTUTES OR 200 PPM AFTER 10 MINUTES. 5 AMP SPDT FAN RELAY CONTROLS STARTERS OF EXHAUST FANS. A 0.5 AMP N.O. ALARM RELAY CONNECTS TO WARNING DEVICES OR CONTROL PANELS. |
BRQN | MEDIA DETECTED | CARBON MONOXIDE |
CXCY | III PART NAME ASSIGNED BY CONTROLLING AGENCY | CARBON MONOXIDE DETECTOR AND CONTROLLER |
ALBY | USAGE DESIGN | INDUSTRIAL |
ALXZ | SPECIFIC USAGE DESIGN | DESIGNED FOR CO DETECTION AND AUTOMATED EXHAUST FAN CONTROL IN AUTOMOTIVE MAINTENANCE FACILITES, ENCLOSED PARKING GARAGES, WAREHOUSES WITH FORKLIFTS, ETC. |
AMKD | INDICATOR TYPE | RED LIGHT AND HORN |